Optimization Of 20 Kv Distribution Transformer Reliability Through Phase R Busbar Temperature Reduction At PT Wilmar Nabati Indonesia
DOI:
https://doi.org/10.33021/6fz6yc75Abstrak
A 20 kV distribution transformer is a critical component for ensuring continuous electricity supply in industrial production. However, continuous operation in harsh industrial environments often causes thermal degradation in Phase R busbars, risking unscheduled downtime and severe financial losses. To address this urgency, comprehensive maintenance activities—focusing on removing surface contamination and optimizing mechanical connections—were implemented at PT Wilmar Nabati Indonesia. A quantitative descriptive case study evaluated the outdoor transformer by comparing field conditions before and after maintenance. The operational parameters analyzed included busbar resistance, heat transfer rate, flour dust contamination, bolt clamping force, and current density. Field measurements encompassed busbar temperature, load current, ambient temperature, humidity, and visual inspection data, with all numerical calculations performed using MATLAB R2022a. The results demonstrated that maintenance significantly improved the busbar's thermal condition. The maximum busbar temperature decreased from 136.3 °C to 70.0 °C, while the average temperature dropped by 41.94 °C. Additionally, the average heat transfer rate fell by 53.77 percent. The estimated bolt clamping force achieved 25 kN, while current density remained stable post-maintenance. Ultimately, eliminating contamination and enhancing mechanical integrity effectively mitigated excessive busbar heating, thereby safeguarding the distribution transformer's operational reliability.







