Optimization Of 20 Kv Distribution Transformer Reliability Through Phase R Busbar Temperature Reduction At PT Wilmar Nabati Indonesia

Authors

DOI:

https://doi.org/10.33021/6fz6yc75

Abstract

A 20 kV distribution transformer is a critical component for ensuring continuous electricity supply in industrial production. However, continuous operation in harsh industrial environments often causes thermal degradation in Phase R busbars, risking unscheduled downtime and severe financial losses. To address this urgency, comprehensive maintenance activities—focusing on removing surface contamination and optimizing mechanical connections—were implemented at PT Wilmar Nabati Indonesia. A quantitative descriptive case study evaluated the outdoor transformer by comparing field conditions before and after maintenance. The operational parameters analyzed included busbar resistance, heat transfer rate, flour dust contamination, bolt clamping force, and current density. Field measurements encompassed busbar temperature, load current, ambient temperature, humidity, and visual inspection data, with all numerical calculations performed using MATLAB R2022a. The results demonstrated that maintenance significantly improved the busbar's thermal condition. The maximum busbar temperature decreased from 136.3 °C to 70.0 °C, while the average temperature dropped by 41.94 °C. Additionally, the average heat transfer rate fell by 53.77 percent. The estimated bolt clamping force achieved 25 kN, while current density remained stable post-maintenance. Ultimately, eliminating contamination and enhancing mechanical integrity effectively mitigated excessive busbar heating, thereby safeguarding the distribution transformer's operational reliability.

Author Biographies

  • Hendriko Joel Siregar, Mercu Buana University

    He was born in Sibolga, Indonesia, on October 30, 2026. He received the Diploma III (D3) degree in electrical engineering from Politeknik Negeri Medan, Medan, Indonesia. He is currently pursuing a Bachelor’s degree (S1) in electrical engineering at Universitas Mercu Buana, Jakarta, Indonesia. His academic interests include electrical power systems, electrical equipment, and industrial electrical systems.

  • Imelda Uli Vistalina Simanjuntak, Mercu Buana University

    She was born in North Sumatra Province, Indonesia, in 1983. She received the B.S. degree from the University of Telkom Bandung, Indonesia in 2008 and the M.Eng. degree from the University of Mercu Buana, Indonesia, in 2012, both in electrical engineering. She is currently pursuing the Ph.D. degree with the school of electrical engineering and informatics in Bandung Institute of Technology, Indonesia. Her research interests include antenna and propagation, array signal processing, and information theory.

Downloads

Published

2026-10-24

Issue

Section

Articles

How to Cite

Optimization Of 20 Kv Distribution Transformer Reliability Through Phase R Busbar Temperature Reduction At PT Wilmar Nabati Indonesia. (2026). Journal of Electrical And Electronics Engineering, 4(1), 25-31. https://doi.org/10.33021/6fz6yc75